Mandatory Building Inspections in a Polish Wspólnota

By Ilia SotoninBuilding inspections, Przeglady budynku, Wspolnota mieszkaniowa
Download Word (.docx)Download PDF

Opens the browser's print dialog. Only the calendar below is printed. Free, no sign-up.

In a Polish wspólnota mieszkaniowa (housing community), the mandatory checks are the periodic inspections of Article 62 of the Building Law: annual, five-yearly, twice a year in large buildings, and inspections after events such as a fire or flood. A person with the right qualifications carries them out and draws up the protocol themselves. Below: what is mandatory, who does it, how often, what the protocol looks like, and an inspection calendar to print.

Checked on 21 November 2026 against the Building Law (consolidated text, Dz.U. 2026 item 524 as amended), the Act on Ownership of Premises, the regulation on the building logbook and GUNB's published guidance. This is general information, not legal advice. What we could not confirm is listed at the end. The Polish article is the original; the forms linked here are in Polish.

Which inspections are mandatory

Article 62(1) of the Building Law says buildings must be inspected during use by the owner or manager. The Building Law never mentions the wspólnota, so who counts as "the owner or manager" in your wspólnota is covered below. The kinds of inspection:

| Inspection | How often | What it covers | Who carries it out | Basis | |---|---|---|---|---| | Annual | at least once a year | weather-exposed elements, environmental-protection installations, gas installations, chimney ducts | a person with building qualifications; gas also a person with supervision qualifications; flue and gravity ducts also a master chimney sweep, mechanical-draught ducts only a person with building qualifications | Art. 62(1)(1), paras 4–6 | | Five-yearly | at least once every 5 years | technical condition and fitness for use, appearance and surroundings, electrical and lightning-protection installations | a person with building qualifications; electrical also a person with supervision qualifications | point 2, paras 4–5 | | Twice a year | by 31 May and by 30 November | the annual scope, in a building with a footprint over 2000 m² | a person with building qualifications | point 3 | | After an event | every time | safe use after the circumstances of Art. 61(2), including fires and floods | a person with building qualifications | point 4 | | After residents' report | within 3 days of the report | inspection after a report of unjustified interference or violations | a person with building qualifications | point 4a, para 2a |

A building with a footprint over 2000 m² is inspected twice a year. What counts is the footprint, the ground the building occupies, not the floor area of the flats. A typical block is below that line; a large complex in one building may exceed it. For such buildings the inspector also notifies the building inspectorate within 7 days (Article 62b(2)); according to the Chief Inspector (GINB), notification is always due, even when no damage was found.

Article 62 says "at least once a year" and gives no date in the year. We also found nothing settling whether that means a calendar year or 12 months from the previous inspection.

Printable inspection calendar

Print the calendar below and fill in the dates. The law requires the inspections; the calendar is our practical aid and does not replace the building logbook. The regulation also says Table I of the logbook records the periodic inspections that are required, within the scope of Article 62(1)(1)-(3) (§ 4(6)). The calendar is in Polish, the language of the forms and protocols.

KALENDARZ PRZEGLĄDÓW BUDYNKU WSPÓLNOTY MIESZKANIOWEJ
Budynek (adres): ____________________________   Rok: __________
Powierzchnia zabudowy: ______ m2 (ponad 2000 m2: kontrola dwa razy w roku)

1. KONTROLA ROCZNA: ELEMENTY BUDYNKU I OCHRONA ŚRODOWISKA (art. 62 ust. 1 pkt 1 lit. a i b)
Co najmniej raz w roku. Kontroler: osoba z uprawnieniami budowlanymi (ust. 4).
Ostatnia: ____________   Następna: ____________   Protokół nr: ____________   Kontroler: ____________

2. KONTROLA ROCZNA: INSTALACJE GAZOWE (art. 62 ust. 1 pkt 1 lit. c)
Co najmniej raz w roku. Kontroler: osoba z uprawnieniami budowlanymi albo z kwalifikacjami dozorowymi (ust. 4 i 5).
Ostatnia: ____________   Następna: ____________   Protokół nr: ____________   Kontroler: ____________

3. KONTROLA ROCZNA: PRZEWODY KOMINOWE (art. 62 ust. 1 pkt 1 lit. c)
Co najmniej raz w roku. Dymowe i grawitacyjne: mistrz w rzemiośle kominiarskim albo osoba z uprawnieniami budowlanymi (ust. 6). Z ciągiem mechanicznym: tylko osoba z uprawnieniami budowlanymi (ust. 6 pkt 2). Protokół w systemie CEEB.
Ostatnia: ____________   Następna: ____________   Numer protokołu CEEB: ____________   Kontroler: ____________

4. KONTROLA PIĘCIOLETNIA (art. 62 ust. 1 pkt 2)
Co najmniej raz na 5 lat: stan techniczny, estetyka, instalacja elektryczna i piorunochronna.
Ostatnia: ____________   Następna: ____________   Protokół nr: ____________   Kontroler: ____________

5. KONTROLA DWA RAZY W ROKU (art. 62 ust. 1 pkt 3), tylko budynek o powierzchni zabudowy ponad 2000 m2
Do 31 maja i do 30 listopada. Kontroler zawiadamia organ nadzoru budowlanego w ciągu 7 dni (art. 62b ust. 2).
Wiosna: ____________   Jesień: ____________   Zawiadomienie organu: ____________   Kontroler: ____________

6. KONTROLA PO ZDARZENIU (art. 62 ust. 1 pkt 4)
Każdorazowo po okolicznościach z art. 61 pkt 2, m.in. po pożarze lub powodzi.
Data zdarzenia: ____________   Data kontroli: ____________   Protokół nr: ____________

7. KONTROLA PO ZGŁOSZENIU MIESZKAŃCÓW (art. 62 ust. 1 pkt 4a, ust. 2a)
W ciągu 3 dni od otrzymania zgłoszenia nieuzasadnionej ingerencji lub naruszenia.
Data zgłoszenia: ____________   Data kontroli: ____________   Protokół nr: ____________

PO KAŻDEJ KONTROLI
[ ] Kontroler wpisał kontrolę do książki obiektu budowlanego w ciągu 7 dni (art. 62b ust. 1). Data wpisu: ____________
[ ] Protokół dołączono do książki (właściciel, zarządca lub osoba upoważniona; według GUNB ustawa nie określa terminu). Data: ____________
[ ] Sprawdzono wykonanie zaleceń z poprzedniej kontroli (art. 62 ust. 1a)
[ ] Uszkodzenia zagrażające usunięto w czasie kontroli lub bezpośrednio po niej (art. 70 ust. 1): tak / nie / nie dotyczy

Przeglądy poza art. 62 (gaśnice, hydranty, windy, czyszczenie kominów): nie omawiamy ich tutaj.

Who carries out the inspections

The law names the inspector's qualifications. The general rule (our English rendering of Article 62(4)): the inspections referred to in paragraph 1, subject to paragraphs 5–6a, are carried out by people holding building qualifications in the relevant specialty. For electrical, lightning-protection and gas installations there is an additional route (paragraph 5): people holding the qualifications required for supervising the operation of energy and gas equipment, installations and networks may carry them out.

Which kind of certificate that means follows from rules we did not read: ask the contractor or a lawyer. For chimney ducts, Article 62(6)(1) gives the inspection to people with a master chimney sweep's qualification as regards flue ducts and gravity exhaust and ventilation ducts. People with building qualifications in the relevant specialty may inspect the same ducts, as well as industrial chimneys, free-standing chimneys and ducts with draught forced by mechanical devices (point 2). GUNB writes that the choice of whom to commission belongs to the owners and managers.

Who is the "owner or manager" in a wspólnota? The Building Law does not use the word "wspólnota" at all. The management board "runs the affairs of the wspólnota and represents it externally" (Article 21(1) of the Act on Ownership of Premises), and the board or a manager entrusted with management in the way set out in Article 18(1) takes over the technical documentation, including the building logbook (Article 29(1b)). We read this as the board or such a manager ordering the inspections. That is our reading, not a provision stated outright, and a question for a lawyer: whom the law means and whom a penalty would hit.

What the inspection protocol is

The person carrying out the inspection draws up the protocol, not the board (Article 62a(1)). As a minimum, Article 62a(2) lists: the date; the inspector's name, building-qualification number with specialty, and signature; the name of the owner or manager; the building inspected; the scope; the findings, with irregularities; the recommendations; the methods and means of use of elements exposed to weather, when those are inspected; and the recommendations of earlier protocols that were not carried out. Recommendations state the actions and the deadline for them (paragraph 3). Copies of the certificate referred to in Article 12(7) and of the decision granting the qualifications are attached (paragraph 4), unless the inspector or the qualifications are entered in the central register (paragraph 4a).

In the texts we read, there is no official model for the whole protocol. We have two practical forms based on Article 62a(2), with room for recommendations and deadlines (both in Polish):

Does the five-year inspection replace the annual one? We found no such provision: Article 62(1) describes two separate scopes. Whether they can be combined in one date and one protocol is a question for a lawyer.

Chimney-sweep inspection in an apartment block

It is mandatory: it is part of the annual inspection (Article 62(1)(1)(c)). GUNB reads the provision as covering all ventilation chimney ducts, gravity and mechanical. There is no paper form for the chimney protocol, because it has its own mode: under Article 62a(5) it is drawn up as an electronic document using the IT system that serves the central register of building emissions (CEEB), and GUNB confirms that these protocols are always drawn up in CEEB. The model to be set by the Chief Inspector of Building Control concerns only this protocol (Article 62a(6)).

Who pays for a chimney-sweep inspection? We did not find an answer in the texts we read. The Act on Ownership of Premises lists, among the costs of managing the common property, "in particular" spending on repairs and current maintenance (Article 14(1)), and puts the upkeep of a flat on its owner (Article 13(1)), but it does not name inspections. A question for a lawyer, with the wspólnota's resolutions and contract at hand.

Gas and electrical installations: how often

Gas installations are checked as part of the annual inspection, so at least once a year. The electrical and lightning-protection installation is tested as part of the five-year inspection, so at least once every 5 years. Whether the gas and chimney inspection reaches inside the flats is not stated in the texts we read. The board may demand access to a flat when it is necessary for maintenance, renovation or removing a breakdown in the common property (Article 13(2) of the Act on Ownership of Premises). That provision does not name inspections, so agree the rules of access for inspections with a lawyer.

After the inspection

  • The entry in the building logbook within 7 days of the end of the inspection is made by the person who carried it out, in the electronic logbook in the c-KOB system or on paper (Article 62b(1)).
  • Attaching the protocol to the logbook is, according to GUNB, a duty of the owner, the manager or the person authorised to keep the logbook. According to GUNB, no deadline is set for attaching it, and seven days is the office's suggestion, not a rule. The logbook and its deadline for going digital are covered in a separate article: c-KOB for a wspólnota.
  • Damage that creates a danger must be removed during the inspection or right after it, if it could endanger life or health, property safety or the environment (Article 70(1)). The protocol confirms it, and the inspector promptly sends a copy to the building inspectorate (Article 70(2)).
  • Other irregularities have their own deadline in the recommendation (Article 62a(3)), and the next inspection checks that they were carried out (Article 62(1a)).

A residents' report: 3 days

If people living in a flat report interference or violations that are not justified by technical or use considerations and that leave the conditions of Article 5(2) unmet, the owner or manager must carry out an inspection within 3 days of receiving the report (Article 62(1)(4a) and (2a)). That is an inspection, not a repair, and it covers only such reports, not every fault. An ordinary fault can be reported, for example, by letter: Pismo do wspólnoty o usunięcie usterki: wzór (in Polish).

The penalty

Article 93(8) covers failing to meet the duty in Article 62(1)(1)-(4a) or Article 62b, and the offender "is liable to a fine". The provision gives no amount. The scale of fines under the Code of Petty Offences and the question of who is responsible in your wspólnota are covered in the article on the building logbook, because they concern the same provisions.

What we could not confirm

  • The date of the annual inspection within the year, and whether "once a year" runs from the calendar year or from the last inspection.
  • Whether the five-year inspection replaces the annual one, and whether both may share one protocol. Ask a lawyer.
  • Who pays for the chimney-sweep and gas inspection, including inside a flat. Ask a lawyer.
  • Whether ordering an inspection is an act of ordinary management and whether a resolution is needed. Ask a lawyer.
  • Who the "owner or manager" is in a wspólnota within the meaning of Article 62.
  • Whether the gas and chimney inspection reaches inside the flats.
  • Which qualification certificate electrical and gas inspections need.
  • Inspections we do not cover: fire extinguishers and hydrants, lifts, playgrounds and periodic chimney cleaning come from other rules that we did not read.

Where Unitify helps

Unitify helps with the work around inspections. You keep documents and protocols separately for each building, and you can record the date of each inspection as a ticket in the calendar. You run the recommendations from a protocol as tracked requests, and you send notices about the inspection date to owners from one panel. More on the Poland page.

Book a demo if you want to see it on your own buildings.

Sources

Topics:Building inspectionsPrzeglady budynkuWspolnota mieszkaniowa

Frequently asked questions

Which building inspections are mandatory in a wspólnota mieszkaniowa?

The Building Law (Article 62(1)) lists periodic inspections: at least once a year (weather-exposed elements, environmental-protection installations, gas installations and chimney ducts), at least once every 5 years (technical condition, appearance, electrical and lightning-protection installations), and twice a year, by 31 May and by 30 November, for buildings with a footprint over 2000 m². On top of that come inspections after events such as a fire or flood, and within 3 days of a report by residents of unjustified interference or violations.

How often must a building be inspected?

The technical-condition inspection, with the electrical and lightning-protection check, at least once every 5 years (Article 62(1)(2)). The annual inspection separately, at least once a year (point 1). The text does not say whether the five-year inspection replaces the annual one of the same year: we found no such provision, so ask a lawyer.

Who carries out building inspections?

As a rule, people holding building qualifications in the relevant specialty (Article 62(4)). Electrical, lightning-protection and gas installations may also be inspected by people with the qualifications required for supervising the operation of energy and gas equipment, installations and networks (paragraph 5). Flue and gravity-ventilation ducts should be inspected by people with a master chimney sweep's qualification (paragraph 6(1)). Ducts with draught forced by mechanical devices, including mechanical ventilation, are inspected by people with building qualifications in the relevant specialty (paragraph 6(2)); according to GUNB, chimney sweeps may not carry out these inspections.

What does the inspection protocol contain?

The person carrying out the inspection draws up the protocol, which must contain at least the date, the inspector's name, signature and building-qualification number, the owner or manager, the building inspected, the scope, the findings, the recommendations and the recommendations from earlier protocols that were not carried out (Article 62a(1) and (2)). In the texts we read, the rules do not set a model for the whole protocol. We have practical forms: a protocol for the annual inspection and one for the five-year inspection.

Is a chimney-sweep inspection mandatory in an apartment block?

Yes. Checking the technical condition of chimney ducts (flue, exhaust and ventilation) is part of the annual inspection (Article 62(1)(1)(c)). The chief building inspectorate (GUNB) reads this as covering all ventilation ducts, gravity and mechanical. The chimney protocol is drawn up in the CEEB system, not on a paper form.

Who pays for a chimney-sweep inspection in an apartment block?

We did not find an answer in the texts we read. The Act on Ownership of Premises lists spending on repairs and current maintenance as management costs (Article 14) and spending on a flat's upkeep as the owner's cost (Article 13(1)), but neither provision names inspections. This is a question for a lawyer, with the wspólnota's resolutions and contracts at hand.

Is ordering an inspection an act of ordinary management?

We found no such provision. Article 22(1) of the Act says the management board takes acts of ordinary management on its own, and the list of acts beyond ordinary management in Article 22(3) is open and does not name inspections. Whether a resolution is needed, including for a multi-year contract, is a question for a lawyer.

How often is a gas installation inspection due in an apartment block?

Checking the technical condition of gas installations is part of the annual inspection, so at least once a year (Article 62(1)(1)(c)). Whether it reaches inside the flats and who pays for it there, we did not find in the texts we read: ask a lawyer.

How often is an electrical inspection due in an apartment block?

Testing the electrical and lightning-protection installation is part of the five-year inspection, so at least once every 5 years (Article 62(1)(2)). Which kind of qualification certificate the person testing the installation needs follows from rules we did not read: ask the contractor or a lawyer.

Is there a penalty for skipping inspections?

Article 93(8) of the Building Law provides a fine for failing to meet the duty in Article 62(1)(1)-(4a) or Article 62b. The provision gives no amount. Who in your wspólnota is responsible is a question for a lawyer.

What about fire extinguisher and lift inspections and chimney cleaning?

We do not cover them in this article. They come from separate rules that we did not read.